Industrial AC Voltage Stabilisers MVRI Series
- Three-Phase Air Cooled
- with Independent Phase Control

MVRI Series - Three Phase Air Cooled AC Voltage Stabilizers - 250 to 2000 kVA
MVRI Series Air Cooled Voltage Stabilisers utilize Magnetic Induction Brushless Technology to deliver highly reliable and virtually maintenance-free voltage stabilisation and protection.
As standard, all MVRI Voltage Stabilisers offer independent phase control ensuring that each phase voltage remains stable, irrespective of load unbalance – even for situations where a 100% load unbalance may exist.
The Stabilisers can be supplied configured for either a Three Phase 4 Wire (With a Neutral) or 3 Wire (Without a Neutral) input supply.
Models are available in 11 different power ratings from 250 to 2000 kVA, being able to accommodate situations where the incoming nominal utility supply is either 380 to 415V (H/HD Series), 190 to 240V (LY/LD Series), or 440 to 480V (HX/HXD Series).
Where required, the Stabilisers can be provided as enhanced Power Conditioning solutions with the inclusion of an Isolation Transformer and/or with a standalone Main System Switchboard (MSB) – with interlocked input, output, and bypass breakers. In addition, on special request, MVRI Stabilisers and their associated switchboards can be supplied as fully standalone containerized power plant solutions.
To learn more about our range of Three-Phase Air Cooled Magnetic Induction Voltage Stabilisers available from Sinalda UK, please check out the following listings, or download the brochure below:
Standard Features include:
- Automatic Voltage Regulation
Step-less automated voltage regulation – ideal for 95% of all applications. - Wide Range of Power Ratings
Three Phase 250 to 2000 KVA - Broad Permissible Input Voltage Swing Ranges
Input Swing – ±10% (S10), ±15% (S15), ±20% (S20), ±25% (S25), ±30% (S30), ±35% (S35) & ±40% (S40) – to specify. - High Efficiency
Better than 97% for low running costs. - Precise Output Voltage Regulation
Output Voltage Accuracy ±1.5% - Transient Voltage Surge Suppression
TVSS – Protects loads against harmful high-energy surges, transients, and spikes. - Independent Phase Control
Independent phase voltage sensing and control to ensure the individual phase voltages remain stable – regardless of load unbalance. - Inbuilt High Overload Capability
Ideal for loads with an inherent initial high current draw on startup. - Lightning Surge Protection
Protection against extremely high voltage surges and transients caused by lightning strikes on the supply line. - Over / Low Voltage Alarm
Audible alarm in the event of the input supply voltage going outside the input voltage window. - Phase Failure & Reversal Alarm
Audible alarm in the event of phase failure or reversal. - Voltage & Current Metering
Analog metering of output voltage and loading with phase selector switches. - Remote Operational Status Monitoring
No Volt Contacts delivering basic operational system status information for use by remote monitoring/building management systems. - Compliance with International Standards
Designed, manufactured, and supplied to comply with leading international standards. - Warranty
2 Years / 24 Months as Standard.
Optional Features available include:
- Power Conditioning (-PC)
Addition of a shielded isolation transformer, to provide enhanced spike & electrical noise (Common Mode: 120db @ 100khz & Normal Mode Noise: 60db @ 100khz) suppression and neutral ground bonding. Delivers what is commonly referred to as a ‘CLEAN’ supply. - Optional Main Switchboard (-MSB)
Floor Standing Main Switchboard with Input & Output Circuit Breakers, Manual Maintenance Bypass, and Metering. - Earth Leakage Relay (-ELCB)
Disconnection of the Power in the event of an earth leakage. - Outdoor IP54 Enclosure (-IP54)
Outdoor IP54 Enclosure (-IP54): IP54 / NEMA 3 style free-standing steel cubicles suitable for external use, or more challenging internal environments.

SELECT | Permissible Input Voltage Window Options (–S*):
| Swing Options | Nominal Voltage | Max Model Rating | |||
|---|---|---|---|---|---|
| 380/220V | 400/230V | 415/240V | |||
| S10 | ±10% | 342 to 418V / 198 to 242V | 360 to 440V / 207 to 253V | 374 to 457V / 216 to 264V | 2000 kVA |
| S15 | ±15% | 323 to 437V / 187 to 253V | 340 to 460V / 196 to 265V | 353 to 477V / 204 to 276V | 2000 kVA |
| S20 | ±20% | 304 to 458V / 176 to 264V | 320 to 480V / 184 to 276V | 332 to 498V / 192 to 288V | 2000 kVA |
| S25 | ±25% | 285 to 475V / 165 to 275V | 300 to 500V / 173 to 288V | 311 to 519V / 180 to 300V | 2000 kVA |
| S30 | ±30% | 266 to 494V / 154 to 286V | 280 to 520V / 161 to 299V | 291 to 540V / 168 to 312V | 1000 kVA |
| S35 | ±35% | 247 to 513V / 143 to 297V | 260 to 540V / 150 to 311V | 270 to 560V / 156 to 329V | 1000 kVA |
| S40 | ±40% | 228 to 532V / 132 to 308V | 240 to 560V / 136 to 322V | 249 to 581V / 144 to 336 | 1000 kVA |
SELECT | Required Power Rating:
| Power Rating (kVA) | Max Rating (Amps per Phase) | MVRI Model No (S*=Add Swing Option No) | ||
|---|---|---|---|---|
| 380/220V | 400/230V | 415/240V | ||
| 250 kVA | 379A | 360A | 347A | MVRI-250H-3P-S* |
| 300 kVA | 455A | 432A | 417A | MVRI-300H-3P-S* |
| 350 kVA | 531A | 505A | 486A | MVRI-350H-3P-S* |
| 400 kVA | 607A | 577A | 556A | MVRI-400H-3P-S* |
| 500 kVA | 759A | 721A | 695A | MVRI-500H-3P-S* |
| 600 kVA | 911A | 865A | 834A | MVRI-600H-3P-S* |
| 750 kVA | 1139A | 1082A | 1043A | MVRI-750H-3P-S* |
| 1000 kVA | 1518A | 1443A | 1390A | MVRI-1000H-3P-S* |
| 1250 kVA | 1898A | 1803A | 1738A | MVRI-1250H-3P-S* |
| 1500 kVA | 2278A | 2164A | 2086A | MVRI-1500H-3P-S* |
| 2000 kVA | 3037A | 2885A | 2781A | MVRI-2000H-3P-S* |
Note: All MVRI Stabilisers are designed to support the full load at minimum input volts and maximum ambient temperature.

SELECT | Permissible Input Voltage Window Options (–S*):
| Swing Options | Nominal Voltage | Max Model Rating | ||||
|---|---|---|---|---|---|---|
| 190/110V | 200/115V | 208/120V | 220/127V | |||
| S10 | ±10% | 171 to 209V / 99 to 121V | 1870 to 220V / 104 to 126V | 187 to 228V / 108 to 132V | 198 to 242V / 114 to 139V | 1000 kVA |
| S15 | ±15% | 162 to 219V / 94 to 127V | 170 to 230V / 98 to 132V | 177 to 239V / 102 to 138V | 187 to 253V / 106 to 146V | 1000 kVA |
| S20 | ±20% | 152 to 228V / 88 to 132V | 160 to 240V / 92 to 138V | 166 to 250V / 96 to 144V | 176 to 264V / 102 to 152V | 1000 kVA |
| S25 | ±25% | 143 to 238V / 83 to 138V | 150 to 250V / 86 to 144V | 156 to 260V / 90 to 150V | 165 to 275V / 95 to 159V | 1000 kVA |
| S30 | ±30% | 133 to 247V / 77 to 143V | 140 to 260V / 81 to 150V | 146 to 270V / 84 to 156V | 154 to 286V / 89 to 165V | 1000 kVA |
| S35 | ±35% | 124 to 256V / 72 to 148V | 130 to 270V / 75 to 155V | 136 to 280V / 78 to 162V | 143 to 297V / 83 to 171V | 1000 kVA |
| S40 | ±40% | 114 to 266V / 66 to 154V | 120 to 280V / 69 to 161V | 125 to 291V / 72 to 168V | 132 to 308V / 77 to 177 | 1000 kVA |
SELECT | Required Power Rating:
| Power Rating (kVA) | Max Rating (Amps per Phase) | MVRI Model No (S*=Add Swing Option No) | |||
|---|---|---|---|---|---|
| 190/110V | 200/115V | 208/120V | 220/127V | ||
| 250 kVA | 759A | 721A | 693A | 655A | MVRI-250LY-3P-S* |
| 300 kVA | 911A | 865A | 832A | 787A | MVRI-300LY-3P-S* |
| 350 kVA | 1063A | 1010A | 971A | 918A | MVRI-350LY-3P-S* |
| 400 kVA | 1215A | 1154A | 1110A | 1049A | MVRI-400LY-3P-S* |
| 500 kVA | 1518A | 1443A | 1387A | 1311A | MVRI-500LY-3P-S* |
| 600 kVA | 1822A | 1731A | 1665A | 1574A | MVRI-600LY-3P-S* |
| 750 kVA | 2278A | 2164A | 2081A | 1967A | MVRI-750LY-3P-S* |
| 1000 kVA | 3037A | 2885A | 2774A | 2623A | MVRI-1000LY-3P-S* |
Note: All MVRI Stabilisers are designed to support the full load at minimum input volts and maximum ambient temperature.

SELECT | Permissible Input Voltage Window Options (–S*):
| Swing Options | Nominal Voltage | Max Model Rating | |||
|---|---|---|---|---|---|
| 440/256V | 460/265V | 480/277V | |||
| S10 | ±10% | 396 to 484V / 229 to 279V | 414 to 506V / 249 to 305V | 432 to 528V / 249 to 305V | 2000 kVA |
| S15 | ±15% | 374 to 506V / 216 to 292V | 391 to 529V / 225 to 305V | 408 to 552V / 235 to 319V | 2000 kVA |
| S20 | ±20% | 352 to 528V / 203 to 305V | 368 to 552V / 212 to 318V | 384 to 576V / 222 to 332V | 2000 kVA |
| S25 | ±25% | 330 to 550V / 191 to 318V | 345 to 575V / 199 to 331V | 360 to 600V / 208 to 346V | 2000 kVA |
| S30 | ±30% | 308 to 572V / 178 to 330V | 322 to 598V / 186 to 345V | 336 to 624V / 194 to 360V | 1000 kVA |
| S35 | ±35% | 286 to 594V / 165 to 343V | 299 to 621V / 172 to 358V | 312 to 648V / 180 to 374V | 1000 kVA |
| S40 | ±40% | 264 to 616V / 152 to 356V | 276 to 644V / 159 to 371V | 286 to 672V / 166 to 388V | 1000 kVA |
SELECT | Required Power Rating:
| Power Rating (kVA) | Max Rating (Amps per Phase) | MVRI Model No (S*=Add Swing Option No) | ||
|---|---|---|---|---|
| 440/256V | 460/265V | 480/277V | ||
| 250 kVA | 327A | 313A | 300A | MVRI-250HX-3P-S* |
| 300 kVA | 393A | 376A | 360A | MVRI-300HX-3P-S* |
| 350 kVA | 459A | 439A | 420A | MVRI-350HX-3P-S* |
| 400 kVA | 524A | 501A | 481A | MVRI-400HX-3P-S* |
| 500 kVA | 655A | 627A | 601A | MVRI-500HX-3P-S* |
| 600 kVA | 787A | 752A | 721A | MVRI-600HX-3P-S* |
| 750 kVA | 983A | 941A | 901A | MVRI-750HX-3P-S* |
| 1000 kVA | 1311A | 1254A | 1202A | MVRI-1000HX-3P-S* |
| 1250 kVA | 1639A | 1568A | 1503A | MVRI-1250HX-3P-S* |
| 1500 kVA | 1967A | 1882A | 1803A | MVRI-1500HX-3P-S* |
| 2000 kVA | 2623A | 2509A | 2404A | MVRI-2000HX-3P-S* |
Note: All MVRI Stabilisers are designed to support the full load at minimum input volts and maximum ambient temperature.

SELECT | Permissible Input Voltage Window Options (–S*):
| Swing Options | Nominal Voltage | Max Model Rating | |||
|---|---|---|---|---|---|
| 380V | 400V | 415V | |||
| S10 | ±10% | 342 to 418V | 360 to 440V | 374 to 457V | 2000 kVA |
| S15 | ±15% | 323 to 437V | 340 to 460V | 353 to 477V | 2000 kVA |
| S20 | ±20% | 304 to 458V | 320 to 480V | 332 to 498V | 2000 kVA |
| S25 | ±25% | 285 to 475V | 300 to 500V | 311 to 519V | 2000 kVA |
| S30 | ±30% | 266 to 494V | 280 to 520V | 291 to 540V | 1000 kVA |
| S35 | ±35% | 247 to 513V | 260 to 540V | 270 to 560V | 1000 kVA |
| S40 | ±40% | 228 to 532V | 240 to 560V | 249 to 581V | 1000 kVA |
SELECT | Required Power Rating:
| Power Rating (kVA) | Max Rating (Amps per Phase) | MVRI Model No (S*=Add Swing Option No) | ||
|---|---|---|---|---|
| 380V | 400V | 415V | ||
| 250 kVA | 379A | 360A | 347A | MVRI-250HD-3P-S* |
| 300 kVA | 455A | 432A | 417A | MVRI-300HD-3P-S* |
| 350 kVA | 531A | 505A | 486A | MVRI-350HD-3P-S* |
| 400 kVA | 607A | 577A | 556A | MVRI-400HD-3P-S* |
| 500 kVA | 759A | 721A | 695A | MVRI-500HD-3P-S* |
| 600 kVA | 911A | 865A | 834A | MVRI-600HD-3P-S* |
| 750 kVA | 1139A | 1082A | 1043A | MVRI-750HD-3P-S* |
| 1000 kVA | 1518A | 1443A | 1390A | MVRI-1000HD-3P-S* |
| 1250 kVA | 1898A | 1803A | 1738A | MVRI-1250HD-3P-S* |
| 1500 kVA | 2278A | 2164A | 2086A | MVRI-1500HD-3P-S* |
| 2000 kVA | 3037A | 2885A | 2781A | MVRI-2000HD-3P-S* |
Note: All MVRI Stabilisers are designed to support the full load at minimum input volts and maximum ambient temperature.
Models (HDY Series) are also available offering a 4 Wire with Neutral Output.

SELECT | Permissible Input Voltage Window Options (–S*):
| Swing Options | Nominal Voltage | Max Model Rating | |||||
|---|---|---|---|---|---|---|---|
| 190V | 200V | 208V | 220V | 240V | |||
| S10 | ±10% | 171 to 209V | 1870 to 220V | 187 to 228V | 198 to 242V | 216 to 264V | 1000 kVA |
| S15 | ±15% | 162 to 219V | 170 to 230V | 177 to 239V | 187 to 253V | 204 to 276V | 1000 kVA |
| S20 | ±20% | 152 to 228V | 160 to 240V | 166 to 250V | 176 to 264V | 192 to 288V | 1000 kVA |
| S25 | ±25% | 143 to 238V | 150 to 250V | 156 to 260V | 165 to 275V | 180 to 300V | 1000 kVA |
| S30 | ±30% | 133 to 247V | 140 to 260V | 146 to 270V | 154 to 286V | 168 to 312V | 1000 kVA |
| S35 | ±35% | 124 to 256V | 130 to 270V | 136 to 280V | 143 to 297V | 156 to 329V | 1000 kVA |
| S40 | ±40% | 114 to 266V | 120 to 280V | 125 to 291V | 132 to 308V | 144 to 336V | 1000 kVA |
SELECT | Required Power Rating:
| Power Rating (kVA) | Max Rating (Amps per Phase) | MVRI Model No (S*=Add Swing Option No) | ||||
|---|---|---|---|---|---|---|
| 190V | 200V | 208V | 220V | 240V | ||
| 250 kVA | 759A | 721A | 693A | 655A | 601A | MVRI-250LD-3P-S* |
| 300 kVA | 911A | 865A | 832A | 787A | 721A | MVRI-300LD-3P-S* |
| 350 kVA | 1063A | 1010A | 971A | 918A | 841A | MVRI-350LD-3P-S* |
| 400 kVA | 1215A | 1154A | 1110A | 1049A | 962A | MVRI-400LD-3P-S* |
| 500 kVA | 1518A | 1443A | 1387A | 1311A | 1202A | MVRI-500LD-3P-S* |
| 600 kVA | 1822A | 1731A | 1665A | 1574A | 1443A | MVRI-600LD-3P-S* |
| 750 kVA | 2278A | 2164A | 2081A | 1967A | 1803A | MVRI-750LD-3P-S* |
| 1000 kVA | 3037A | 2885A | 2774A | 2623A | 2404A | MVRI-1000LD-3P-S* |
Note: All MVRI Stabilisers are designed to support the full load at minimum input volts and maximum ambient temperature.
Models (LDY Series) are also available offering a 4 Wire with Neutral Output.

SELECT | Permissible Input Voltage Window Options (–S*):
| Swing Options | Nominal Voltage | Max Model Rating | |||
|---|---|---|---|---|---|
| 440V | 460V | 480V | |||
| S10 | ±10% | 396 to 484V | 414 to 506V | 432 to 528V | 2000 kVA |
| S15 | ±15% | 374 to 506V | 391 to 529V | 408 to 552V | 2000 kVA |
| S20 | ±20% | 352 to 528V | 368 to 552V | 384 to 576V | 2000 kVA |
| S25 | ±25% | 330 to 550V | 345 to 575V | 360 to 600V | 2000 kVA |
| S30 | ±30% | 308 to 572V | 322 to 598V | 336 to 624V | 1000 kVA |
| S35 | ±35% | 286 to 594V | 299 to 621V | 312 to 648V | 1000 kVA |
| S40 | ±40% | 264 to 616V | 276 to 644V | 286 to 672V | 1000 kVA |
SELECT | Required Power Rating:
| Power Rating (kVA) | Max Rating (Amps per Phase) | MVRI Model No (S*=Add Swing Option No) | ||
|---|---|---|---|---|
| 440V | 460V | 480V | ||
| 250 kVA | 327A | 313A | 300A | MVRI-250HXD-3P-S* |
| 300 kVA | 393A | 376A | 360A | MVRI-300HXD-3P-S* |
| 350 kVA | 459A | 439A | 420A | MVRI-350HXD-3P-S* |
| 400 kVA | 524A | 501A | 481A | MVRI-400HXD-3P-S* |
| 500 kVA | 655A | 627A | 601A | MVRI-500HXD-3P-S* |
| 600 kVA | 787A | 752A | 721A | MVRI-600HXD-3P-S* |
| 750 kVA | 983A | 941A | 901A | MVSI-750HXD-3P-S* |
| 1000 kVA | 1311A | 1254A | 1202A | MVRI-1000HXD-3P-S* |
| 1250 kVA | 1639A | 1568A | 1503A | MVRI-1250HXD-3P-S* |
| 1500 kVA | 1967A | 1882A | 1803A | MVRI-1500HXD-3P-S* |
| 2000 kVA | 2623A | 2509A | 2404A | MVRI-2000HXD-3P-S* |
Note: All MVRI Stabilisers are designed to support the full load at minimum input volts and maximum ambient temperature.
Models (HXDY Series) are also available offering a 4 Wire with Neutral Output.
General Technical Specification
| General: | ||
| Design Topology: | Brushless Air Cooled Magnetic Induction | |
| Phase: | H, LY & HX Series | Three Phase, 4 Wire (3P+N+GE) |
| HD, LD & HXD Series | Three Phase, 3 Wire (3P+GE) | |
| Model Nos: | MVRI-250*-3P-S* to MVRI-2000*-3P-S* | |
| Power Ratings: | 11 Model Ratings- 250 kVA, 300 kVA, 350kVA, 400kVA, 500kVA, 600kVA , 750kVA, 1000kVA, 1250kVA, 1500kVA & 2000kVA | |
| Frequency: | 47 to 65Hz | |
| Phase Control: | Independent – maintains each phase voltage stable irrespective of load unbalance, even up to 100% load unbalance. | |
| Power Factor: | The Power Factor has no effect on performance providing the stabilizer is being used within its rated capacity | |
| Input: | ||
| Nominal Voltage: | H & HD Series* | 380V, 400V or 415V (Customer to Specify) |
| LY & LD Series* | 190V, 200V, 208V, 220V, or 240V (Customer to Specify) | |
| HX & HXD Series* | 440V, 460V or 480V (Customer to Specify) | |
| Permissible Input Voltage Window/Swing (S*): | S10 – Nominal Voltage ±10% S15 – Nominal Voltage ±15% S20 – Nominal Voltage ±20% S25 – Nominal Voltage ±25% S30 – Nominal Voltage ±30% S35 – Nominal Voltage ±35% S40 – Nominal Voltage ±40% | |
| Output: | ||
| Voltage: | H & HD Series* | 380V, 400V or 415V |
| LY & LD Series* | 190V, 200V, 208V or 220V | |
| HX & HXD Series* | 440V, 460V or 480V | |
| Voltage Accuracy: | ±1.5% | |
| Response Time: | <1.5ms | |
| Correction Time: | A 10% supply variation will be corrected to within 2.5% in typically 0.6 to 1 second – dependent on the selected permissible input voltage swing and system rating | |
| Efficiency: | ≥97% | |
| Metering, Alerts & Communication: | ||
| Metering: | Input Volts, Output Volts, and Load – complete with Phase Selector Switches | |
| Alarms: | Over & Low Volts Loss of Phase & Phase Reversal Over Temperature | |
| Interface: | No-Volt Free Contacts (N.C & N.O) | |
| Protection Features: | ||
| Surge Protection: | TVSS – Protects loads against high-energy Spikes and Transient Voltages | |
| Lightning Surge Arrestors: | SPD – Class II | |
| Overload Protection: | 10 x max. current rating for 2 seconds 3 x max. current rating for 1 minute 2 x max. current rating for 2 minutes | |
| Environmental: | ||
| Operating Temperature Range: | -10°C to +45°C Derate by 2% for each additional °C up to max 60°C | |
| Storage Temperature Range: | -40°C to +50°C | |
| Maximum Altitude: | 1000 meters (derate by 2.5% per additional 500 meters) | |
| Relative Humidity: | Suitable for indoor tropical use – 0 to 95% (non-condensing) | |
| THD – Harmonic Distortion: | < 1% | |
| Physical: | ||
| Power Connections: | Hardwire Input & Output (with top cable entry) | |
| Construction: | IP20 / NEMA 1 Style – BS EN 60529 | |
| Paint Colour: | RAL 7032 (Grey – Epoxy Powder Coating) | |
| Dimensions & Weights: | Dependent on model rating and configuration Sizes and weights available on individual request | |
| Certification & Conformance: | ||
| EMC Conformance: | BS EN 55022 and relevant parts of BS EN 61000 | |
| CE Certification: | CE Marked – 2014/30/EU (The EMC Directive) and 2014/35/EU (The Low Voltage Directive) | |
| Warranty: | 2 Years / 24 Months from date of supply | |
| Optional Add-Ons: | ||
| Main System Switchboard (-MSB): | Floor Standing System Switchboard with – 3 Pole (4 Pole Option) Input Circuit Breaker, Output Circuit Breaker, Manual Maintenance Bypass Switch & Metering & Interlocking Protection | |
| Power Conditioning (-PC): | Addition of a shielded isolation transformer, to provide enhanced spike & electrical noise (Common Mode: 120db @ 100khz & Normal Mode Noise: 60db @ 100khz) suppression and neutral ground bonding. Delivers what is commonly referred to as a ‘CLEAN’ supply | |
| Earth Leakage Relay (-ELCB): | Disconnection of the Power in the event of an earth leakage | |
| Outdoor IP54 Enclosure (-IP54) | Outdoor IP54 Enclosure (-IP54): IP54 / NEMA 3 style free-standing steel cubicles suitable for external use, or more challenging internal environments. | |
Sales & Support
- Data Sheet
- DOCGuide Specification
- PDFOperator / User Manual
CE Certification
MVRI Series Three-Phase Air-Cooled Industrial Voltage Stabilisers comply with the relevant European Union (EU) health, safety, and environmental protection directives and regulations and are duly CE marked.
- PDF
Sinalda UK Declaration
EMC Directive – 2014/30/EU – in force from April 2016
Low Voltage Directive – 2014/35/EU – in force from April 2016
If you do not find the Industrial Voltage Stabiliser that meets your application’s exact needs, please contact us with your specific detailed requirements.